Open loop motion control
12.10 Advanced topics
SM address
SMB623
SMB624
SMB625
SMD626
SMD630
SMB634
SMB635 to SMB645
SMD646
558
Description
Axis 0 Instantaneous status: Reflects the status of the configuration and
rotation direction status
OR (Target speed out of range):
0 = In range
1 = Out of range
R (Direction of rotation):
0 = Positive rotation
1 = Negative rotation
CFG (Module configured):
0 = Not configured
1 = Configured
Axis 0: CUR_PF is a byte that indicates the profile currently being executed.
Axis 0: CUR_STP is a byte that indicates the step currently being executed
in the profile.
Axis 0: CUR_POS is a double-word value that indicates the current position
of the Axis of Motion.
Axis 0: CUR_SPD is a double-word value that indicates the current speed of
the Axis of Motion.
Axis 0: Result of the instruction. Error conditions above 127 are generated
by the instruction subroutines created by the Motion wizard.
D (Done bit):
0= Operation in progress
1= Operation complete (set by the Axis of Motion during initialization)
ERROR: (See "Motion instruction error codes" (Page 545) list.)
Reserved
Axis 0: Pointer to the V memory location of the configuration/profile table. A
pointer value to an area other than V memory is not valid. The Axis of Mo-
tion monitors this location until it receives a non-zero pointer value.
System Manual, 09/2015, A5E03822230-AC