To disable false echo tracking:
1 Select Device Setup > Sensor Setup > False Echo Tracking.
2 Press Edit.
3 Highlight Disable and press OK.
Resetting false echo tracking
There are situations, such as modifications made to the vessel, where false echo tracking might need to
be reset, effectively erasing the false echo history and starting anew.
To reset the tracking of false echoes:
1 Select Device Setup > Sensor Setup > Reset Tracking.
2 Press OK.
False echo tracking is reset and you return to the previous menu.
Setting up the application
Before starting level measurements, you need to set certain hardware parameters regarding the probe,
the vessel and the instrument nozzle. These parameters are set in the Application Setup menu under
the Device Setup menu.
—
Figure 30 The Device Setup menu
Changing the probe type
Your instrument, as delivered, was configured with the type of probe ordered. Should you need to
change the type of probe in the future, you also need to change the type in the LWT instrument.
To do so:
1 Select Device Setup > Application Setup > Probe Type.
2 Press Edit.
3 Highlight the appropriate probe type and press OK.
Changing the probe length
The probe length is already programmed into the instrument. Should you have to physically shorten the
probe for any reason, do not forget to change the probe length programmed in the instrument.
To do so:
1 Select Device Setup > Application Setup > Probe Length.
2 Press Edit.
3 Set the length of the shortened probe and press OK.
Configuring the instrument 45