Event codes and recommendations

Below is a list of the event codes that your LWT instrument might display, should a problem arise. The
first letter of the code refers to NAMUR codes:
• F: Failures
• S: Function check
• C: Out of specifications
• M: Maintenance request
Table 3
Event codes and recommended action
No.
Event message
S080.000
Maximum level rate exceeded
S081.001
GpC alarm, last valid gpc used
F203.002
Surface has lost surface echo
F234.005
Electronic failure or harsh env
F200.010
pV value out of range
C153.011
GpC currently in calibration
S083.012
too many echos detected
F233.013
Reference echo not detected
F210.016
Invalid device parameters
F236.017
Sensor NV Failure
F202.019
Surface inside blocking distance
F237.020
Sensor Board communication error.
F223.023
Electronics NV Failure
S082.024
Weak echo amplitude
F232.025
Loss of RF connection
F201.026
Surface inside safety distance
M030.031
Maintenance required
M010.032
Supply voltage error
M011.033
temperature out of range
F230.034
First coupler seal leak
F235.035
Load sensor configuration failure
C151.036
Data Simulation warning
C150.037
alarm Simulation warning
C152.038
Current output in fixed mode
Recommended action
Make sure that the max level rate matches the process.
Check installation, GpC marker position, buildup and
process conditions.
Check installation and parameter adjustments.
Check installation for high vibrations or EMC interference.
Check process conditions and/or device configuration
Wait for calibration to finish.
Check installation or device parameters.
Check installation and coupler connection.
Enter valid parameters.
the sensor should be replaced as soon as possible.
Check process conditions and device configuration.
Restart the device. If condition persists, call aBB for
replacement.
the electronics must be replaced; call aBB.
Check installation and process conditions.
Check the connection between the instrument head and the
coupler.
Check process conditions and device configuration.
Verify instrument functionality and clear the diagnostic
message.
Make sure that power supply voltage at the device terminal
is between 15.5 V DC and 42 V DC.
Check ambient temperature
Use instrument with remote option
Check coupler.
Restart the device. If condition persists, call aBB for
replacement.
the level value produced in output is derived by the value
simulated in input
an alarm condition is being simulated by the device.
Output current is in fixed mode. this could be due to the
device being used in multidrop mode or a simulation.
Maintenance and troubleshooting
69