To configure with the Easy Setup menu:
1 Press Select. The Language menu appears immediately.
a Press Edit. The list of available languages appears (default value: English).
b Scroll up or down the list and highlight the desired language.
c Press OK . The interface changes to the selected language immediately.
For more information, see "Language" on page 37.
2 Press Next. The Set PV (4-20mA) screen appears. This sets the type of measurement that you want
to make.
a Press Edit. The list of available measurements appears (default value: Level).
b Scroll up or down the list and highlight the required measurement.
c Press OK. The measurement is selected.
For more information, see "Setting up the primary value (PV)" on page 43.
3 Press Next. The PV Unit screen appears. This sets the measurement unit for the measurement type
that you just previously selected.
a Press Edit. The list of available measurement units appears (default value: cm)
b Scroll up or down the list and highlight the required measurement unit.
c Press OK. The measurement unit is selected.
For more information, see "Selecting the primary value unit" on page 43).
4 Press Next. The Empty/Zero screen appears. This sets the lowest level that you expect to measure
in the vessel.
a Press Edit.
b Set the required value (see "Setting a value" on page 31).
c Press OK. The value is set.
For more information, see "Changing the empty/zero value" on page 59.
5 Press Next. The Full/Span screen appears. This sets the highest level that you expect to measure in
the vessel.
a Press Edit.
b Set the required value (see "Setting a value" on page 31).
c Press OK. The value is set.
For more information, see "Changing the full/span value" on page 60.
6 Press Next. The Application Category screen appears. This sets the process in which level
measurements will be made, based on the dielectric constant (DC) of the vessel content.
a Press Edit. The list of available values appears (default value: Water-based (DC>10))
b Scroll up or down the list and highlight the required value.
c Press OK. The value is applied.
For more information, see "Selecting the application category" on page 44.
34
User Guide