Figure 2-1. Powerware 9390 40–80 kVA UPS Cabinet as Shipped on Pallet
The UPS cabinet is heavy (see Table A on page A-3). If unpacking instructions are not closely
followed, the cabinet may tip and cause serious injury.
1. Carefully inspect the outer packaging for evidence of damage during transit.
Do not install a damaged cabinet. Report any damage to the carrier and contact your
Powerware service representative immediately.
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site,
or as close as possible, before unpacking. Insert the forklift or pallet jack's forks
between the pallet supports on the bottom of the unit.
NOTE
Verify that the forklift or pallet jack is rated to handle the weight of the cabinet
(see Table A on page A-3 for cabinet weight).
Do not tilt the UPS cabinet more than 10° from vertical or cabinet may tip over.
UPS Installation Plan and Unpacking
C A U T I O N
C A U T I O N
C A U T I O N