Powerware 9390 Installation & Operation Manual page 127

40-80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

1.
Use Class 1 wiring methods (as defined by the NEC) for control wiring. The wire should be
rated at 24 volts, 1A minimum.
2.
When installing interface wiring (e.g., building alarm, relay output, battery breaker trip and
X---Slot) to the UPS interface terminals, conduit must be installed between each device and
the UPS cabinet. Install the interface wiring in separate conduit from the power wiring.
3.
All building alarm inputs or remote features require an isolated normally-open contact or
switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and
common terminal as shown. All control wiring and relay and switch contacts are customer
provided.
4.
Regardless of assignment, alarms display as Building Alarm 1 and Building Alarm 2,
on the Control Panel Display Screen. Use twisted---pair wires for each alarm input and
common.
5.
Refer to Table M through Table P and to Chapters 3 and 5 for customer interface wiring.
6.
LAN and telephone drops, for use with X---Slot connectivity cards, must be provided by
facility planners or customer.
Table M. TB1 and TB2 Interface Connections
Terminal TB1
1
2
3
4
5
6
7
8
9
10
Terminal TB2
1
2
3
4
5
6
7
8
9
10
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev A
®
Name
Building Alarm 1
Building Alarm 2
Building Alarm Return
Alarm Relay NC
Alarm Relay Com
Alarm Relay NO
External EPO NO
External EPO NC
External EPO Com
Not Used
Name
Not Used
Not Used
Battery Aux +
Battery Aux ---
Battery UVR +
Battery UVR ---
On Bypass Relay
On Bypass Relay Return
On Inverter Relay
On Inverter Relay Return
Description
Programmable UPS alarm. Activated by a remote
Programmable UPS alarm Activated by a remote
dry contact closure.
dry contact closure
General purpose normally-open and normally-closed
General purpose normally open and normally closed
relay contacts.
relay contacts
Normally-open and normally-closed dry contacts
Normally open and normally closed dry contacts
used to activate EPO of UPS from a remote switch.
used to activate EPO of UPS from a remote switch
Description
Contacts used to indicate whether UPS battery
Contacts used to indicate whether UPS battery
breaker or disconnect is open or closed.
Contacts used to open battery breaker or
Contacts used to open battery breaker or
disconnect.
Normally open contact closes when UPS is on
Normally-open contact closes when UPS is on
bypass.
Normally closed contact opens when output
Normally-closed contact opens when output
contactor closes.
DESCRIPTION:
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL LOCATIONS
DRAWING NO:
164201535---8
REVISION:
A
Installation Information
SHEET:
1 of 5
DATE:
062504
A-19