Powerware 9390 Installation & Operation Manual page 116

40-80 kva
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Installation Information
Table F. INPUT/OUTPUT Ratings & External Wiring Requirements for 9390-- 80/80
Basic unit ratings:
0.8 lagging pF load
gg g
AC Input to UPS Rectifier
AC Input to UPS Rectifier
AC
AC
3 , 1 Neutral, 1 gnd
3 , 1 Neutral, 1 gnd
INPUT
Minimum conductor size (number per  )
AC Input to UPS Bypass
Full Load Current
Full Load Current
AC
AC
INPUT
Minimum conductor size (number per  )
DC Input from Battery to UPS
(1) positive, (1) negative
DC
INPUT
INPUT
Minimum conductor size (number per  )
AC Output to Critical Load
AC
AC
Full Load Current 3 , (1) Neutral, (1) gnd
Full Load Current 3  (1) Neutral (1) gnd
OUTPUT
Minimum conductor size (number per  )
NOTE: Callout letters
map to drawing 164201535 ---4.
A-8
Ratings
(0.98min.PF)
(0.98min.PF)
*(Includes full load current plus
battery recharge current)
3 , (1) Neutral, (1) gnd
3 , (1) Neutral, (1) gnd
and
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev A
®
Units
kVA
kW
INPUT/OUTPUT
VOLTAGE
Amps*
Amps*
A
AWG or kcmil (ea)
Amps
B
AWG or kcmil (ea)
Vdc
C
Amps @ (2.0V/cell)
AWG or kcmil (ea)
Amps
D
AWG or kcmil (ea)
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201535---5
REVISION:
A
Rating 50/60 Hz
80
80
72
72
208
480
240
240
105
105
2/0 (2)
1/0 (1)
222
96
2/0 (2)
1/0 (1)
384–480
432–480
203
203
3/0 (1)
3/0 (1)
222
96
2/0 (2)
1/0 (1)
SHEET:
2 of 7
DATE:
062504