7.4. Setting function of communication waiting time (

Use this function for the following case:
When the data response from the inverter is too quick after the PC had sent the data to the inverter,
PC process cannot get ready to receive the data, or when the RS485/RS232C converter is used,
changeover of sending and receiving data takes much time in the converter process.
The case of " Inter-drive communication ", set up more than 0.03 seconds as a transmitting interval
on the master side to wait for the processing time on the slave side(
* This function works only when TOSHIBA protocol is selected (
Functional specification:
A time for sending data is prolonged longer than the preset time, until the inverter returns the data
to the PC, after it finishes receiving the data (in case of an inter-drive communication, until the in-
verter returns the next data to the PC, after it has sent the data.) In case the inverter's processing
capacity requires longer setting time, the value more than this time will be the set value. (The pa-
rameter makes the inverter wait for more than the set time.)
Setting range:
If the set value is
maximum capacity of the inverter. To obtain a quick response for sending data, set value
Computer link
PC → INV
Inter-drive
Master INV
communication
to Slave INV
Time elapses more than the transmission
waiting time.
7.5. Free notes(
This parameter allows you to write any data, e.g., the serial number of each inverter or parameter
information, which does not affect the operation of the inverter.
to
seconds (10ms to 2000ms)
, this function becomes invalid and the interval time for sending data is set to the
Time elapses more than
transmission waiting time.
)
47
= ).
Time from the confirmation of the
data reception (transmission, in the
case of inter-drive communication)
to the transmission of data, is
INV → PC
adjusted.
If the inverter's processing time
requires longer time than the
Master INV to
transmission waiting time, the time
Slave INV
is prolonged.