7. Communications parameters

The settings of communication-related parameters can be changed from the operation panel and
the external controller (computer). Note that there are two types of parameters: parameters whose
settings take effect immediately after the setting and parameters whose settings do not take effect
until the inverter is turned back on or reset.
Com-
muni-
cation
Title
Function
Num-
ber.
Communication
0800
baud rate
0801
Parity
0802
Inverter number
Communication
0803
error trip time
Communication
0805
waiting time
Setting of master
and slave invert-
ers for communi-
0806
cation between
inverters (setting
of master and
slave)
0811
Point 1 setting
0812
Point 1 frequency
0813
Point 2 setting
0814
Point 2 frequency
Selection of
0829
communication
protocol
Number of motor
0856
poles for motor
speed
0870
Block write data 1
0871
Block write data 2
0875
Block read data 1
0876
Block read data 2
0877
Block read data 3
0878
Block read data 4
0879
Block read data 5
0880
Free notes
Block communi-
FA80
----
cation for LED
Adjustment range
0: 9600bps
1: 19200bps
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
0-247
0: (disabled)
1-100
0.00-2.00s
0: Slave inverter (0 Hz command issued
in case the master inverter fails)
1: Slave inverter (Operation continued
in case the master inverter fails)
2: Slave inverter (Emergency stop trip-
ping in case the master inverter fails)
3: Master inverter (transmission of fre-
quency commands)
4: Master inverter (transmission of out-
put frequency signals)
0-100
0.0-200.0Hz
0-100
0.0-200.0Hz
0: Toshiba inverter protocol
1: Modbus-RTU protocol
2: Metasys N2 (option)
3: FLN P1 (option)
4: BACnet (option)
1:2pole , 2:4pole .... 8:16pole
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
6: Motor speed command
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
11: Output motor speed monitor
0-65535
0:Disable
1:Enable
44
Default
Unit
Valid
setting
After re-
-
1
set.
After re-
-
1
set.
1
0
Real time
1s
0
Real time
0.01s
0.00
Real time
After re-
-
0
set.
1%
0
Real time
0.01Hz
0.0
Real time
1%
100
Real time
0.01Hz
60.0
Real time
After re-
-
0
set.
-
1
Real time
After re-
set.
0
-
After re-
set.
-
0
1
0
Real time
-
0
Real time
E6581393
Modbus
Reference
protocol
Enable
Section 7.1
Enable
Section 7.1
Enable
Section 7.2
Enable
Section 7.3
Disable
Section 7.4
Disable
Chapter 6
Disable
Disable
Section 6.1
Disable
Disable
Enable
Chapter 3
Enable
Enable
Section
5.1.4
Enable
Section
Section
4.1.3
5.1.2
Enable
Section 7.5
Section
Disable
8.4.1