4. Parameters

4.1. Communication parameters

Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not
set to correct value, this unit can not work normally.
Commu
Title
nication
No.
0831
Network Baudrate (*1)
f831
0832
f832
0833
f833
0834
f834
Operation
0851
at communication error
f851
by disconnection
Preset speed operation
0852
f852
selection
Communication option
0853
station address monitor
f853
(Read Only)
Network option reset
0899
f899
setting
Add-on option 1 CPU
FE66
version(Under side option)
Add-on option 2 CPU
FE67
version(Panel side)
* When fmod or cmod is set to "Communication option input", VF-PS1 drives without
FLN LOC REF (LDO point #69) or FLN LOC CTL (LDO point #68) at each Objects.
(*1): This parameter is effective by reset. Please reset (power supply reset or f899=1)
after changing a set point.
Function
Network Time-Out (*1)
Factory setting (*1)
Station address
Description
0: 9600bps,1: 4800bps,2: 9600bps
3: 19200bps,4: 38400bps,
5: 57600bps,6: 76800bps
Over 7 is 9600bps.
0: No action
Unit 0.1 sec, Setting range: 1 – 1000
Over 1000 is 100.0s.
Except ACh:Reset to factory setting
ACh:Finished with reset to factory setting
1-99
The range outside is converted into 99
0: Inverter stop, communication command,
frequency mode open (by cmod, fmod)
1: None (continued operation)
2: Deceleration stop
3: Coast stop
4: Network error (err8 trip)
5: Preset speed operation (by f852 setting)
0:None
1~15:Preset speed operation (by parameter
setting)
Real station address monitor
If a value of f834 is out of a range, the
value of f853 becomes 99.
0:None
1:Reset option circuit board and inverter
High byte is version Low byte is revision.
For example, When version number 1, and
revision number 2 is, panel indication
becomes with 1.02.
The version of the option with it has equipped
can be checked by using the function of
f710 to f718 (standard monitor display
selection).
*For details, refer to the inverter instruction
manual.
- 11 -
E6581541②
Factory
setting
0000
0000
0000
(ACh)
0000
0
0
0