Toshiba TOSVERT VF-FS1 Instruction Manual page 17

Communications function
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

■ Inverter → Computer
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched.
This is because there will be a risk that the returned data may be deformed.
1) Normal processing
Omissible
Start
INV
CMD
Number
Code
of Read
No.
"Y"
"/"
Data
Groups
1. 2FH "/" (1 byte)
2. INV-NO (1Byte)
3. CMD(1Byte)
4. Number of read data groups (1 byte)
5. Write status (1 byte)
6. Read data1 - 5 (2 bytes)
7.SUM(1Byte)
■ Example
(When set as follows:
=
(status),
=
(alarm)
Computer → Inverter:2F 58 02 05 C4 00 17 70 D9
Inverter → Computer:2F 59 05 03 00 00 00 00 00 00 00 00 00 00 90 (When parameter is not set)
Inverter → Computer:2F 59 05 00 40 00 00 00 00 00 00 00 00 00 CD CD (When parameter is set)
Inverter → Computer:2F 59 05 00 64 00 17 70 1A 8A 24 FD 00 00 3D (During operation at 60Hz)
Number of read data groups x 2 bytes
Write
Read
Read
Read
Status
data1
data1
data2
high
low
high
Checksum area
:Start code in binary mode
:Inverter number・・・00H to 3FH
If the inverter number matches up with that specified from the operation panel, data
will be returned from the inverter. If the inverter number does not match, the data will
be judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the in-
verter number does not match. (Inverter number is considered matched if it is omit-
ted during reception)
:'Y' (Block communication command [monitoring])
Lowercase letter 'y' during an inverter trip, including standing by for retrying and during
a trip.
: Return the number of data groups to be read (00H to 05H).
: Return 00H to 03H.
* Failing to write in the specified parameter in the number of write data groups, set "1"
in the corresponding bit for the parameter failed to write. (See below.)
Bit Position
7
6
Data Type
: Return according to the number of read data groups. "0000H" is returned as dummy
data if "0" is selected as a parameter.
Read data1: Data selected by
Read data3: Data selected by
Read data5: Data selected by
: Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code of return data to read data.
=
(Command 1),
=
(output frequency),
Read
Read
Read
Read
data2
data3
data3
data4
low
high
low
5
4
3
2
1
. Read data2: Data selected by
. Read data4: Data selected by
.
=
(frequency command value),
=
(output current),
16
E6581393
Read
Read
Read
data4
data5
data5
high
low
high
low
0
=
(output voltage) and
SUM
.
.

Advertisement