Alarm information monitor (FC91)
Bit
0
Over-current alarm
1
Inverter overload alarm
2
Motor overload alarm
3
Overheat alarm
4
Overvoltage alarm
5
Main circuit undervoltage alarm
6
(Undefined)
7
Low current alarm
8
Over-torque alarm
9
(Undefined)
Cumulative operation hours
10
alarm
11
(Undefined)
12
(Undefined)
13
Main-circuit voltage error alarm
At the time of the instant black-
14
out, Forced deceleration/stop
An automatic stop during the
15
lower limit frequency continu-
ance
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgement.
Cumulative operation time alarm monitor (FE79)
Bit
0
Fan life alarm
1
Circuit board life alarm
2
Main-circuit capacitor life alarm
3
User set alarm
4-15 (Undefined)
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgement.
Specifications
Specifications
55
0
1
Normal
Alarming
Normal
Alarming
Normal
Alarming
Normal
Alarming
Normal
Alarming
Normal
Alarming
-
-
Normal
Alarming
Normal
Alarming
-
-
Normal
Alarming
-
-
-
-
Normal
Alarming
Decelerating,
-
stopping
Decelerating,
-
stopping
0
1
Normal
Alarm issued
Normal
Alarm issued
Normal
Alarm issued
Normal
Alarm issued
-
-
E6581393
Remarks
(Code displayed on the panel)
flickering
flickering
flickering
flickering
flickering
-
-
-
-
-
-
-
-
"
flickering
Related: F256 setting
Related: F302 setting
Remarks
-
-
-
-
-