■ Inverter → Computer (Abnormal return) *The text size is 5 bytes fixed.
Inverter
Command Error Code
No.
AB
1) Inverter No (1 byte)
2) Command (1 byte)
3) Error code (1 byte)
4) CRC16 (2 bytes)
■ Example: Reading Identification
Inverter No = 01H
Manufacturer name = "TOSHIBA"(7 bytes)
Device name = "VFFS1-2007PM" (12 bytes)
Device version = "0100" (4 bytes)
(Computer → inverter) 01 2B 0E 01 00 70 77
(Inverter → computer) 01 2B 0E 01 01 00 00 03
00 07 54 4F 53 48 49 42 41
01 0C 56 46 46 53 31 2D 32 30 30 37 50 4D
02 04 30 31 30 30
CA 38
CRC16
low
: ---
: ABH fixed (Read command error) (Command + 80H)
: See "5.3. Error codes".
: ---
high
36