8. Commands and monitoring from the computer

Across the network, instructions (commands and frequency) can be sent to each inverter and the
operating status of each inverter can be monitored.

8.1. Communication commands (commands from the computer)

■ Communication command (Communication number: FA00)
Commands can be executed on inverter frequencies and operation stop through communications.
The VF-FS1 series can enable command and frequency settings through communications irrespec-
tive of settings of the command mode (
Forced change from communication to local," "52: Forced operation," or "53: Fire speed" is set by
input terminal function selection (
communication and to a frequency command is feasible through a contact on the terminal board.
Once the communication command (FA00) is set to enable communication command priority and
frequency priority, both priorities will be enabled unless OFF is set, power is turned off or is reset, or
standard shipment setting (
terminal output hold are always enabled even though communication command priority is not set.
Table 1 Data construction of communication commands (communication number: FA00)
bit
Specifications
0
Preset speed operation frequencies 1
1
Preset speed operation frequencies 2
2
Preset speed operation frequencies 3
3
(Reserved)
4
Motor selection (1 or 2) (THR 2 selec-
tion)
5
PI control
6
Acceleration/deceleration pattern se-
lection (1 or 2)
(AD2 selection)
7
DC braking
8
(Reserved)
9
Forward/reverse run selection
10
Run/stop
11
Coast stop command
12
Emergency stop
13
Fault reset
14
Frequency priority selection
15
Command priority selection
Note: Set 0 to reserved bit
Ex.: Forward run: (PFA008400) CR
1 is specified for bit 15 (communication command: enabled) and bit 10 (operation command).
Ex.: Reverse run: (PFA008600) CR, (PFA00C600) CR
8600H : To disable frequency instructions from the computer
C600H : To enable also frequency instructions from the computer
Preset speed operation is disabled or
preset speed operation frequencies
(1-7) are set by specifying bits for preset
speed operation frequencies 1-3.
(000: Preset speed operation OFF,
Normal operation
tion/deceleration
pattern 1 (AD1)
BIT15
FA00:
1
0
0
0
8
) and frequency mode (
to
,
) is selected. Emergency stop, RY terminal output hold and OUT
0
001-111: Setting of preset speed op-
eration frequencies (1-7))
Motor 1
Motor2
(THR 1)
(THR2)
PI OFF
Accelera-
Accelera-
tion/deceleration
pattern 2 (AD2)
OFF
Forced DC braking
Forward run
Reverse run
Stop
Run
Standby
Coast stop
OFF
Emergency stop
OFF
Reset
OFF
Enabled
OFF
Enabled
0
1
0
0
0
0
0
4
0
48
). However, if "48:
), a change to a command other than
1
Remarks
Preset speed operation can
be disabled or a preset
speed operation frequen-
cies (1-7) can be specified
by combining 3 bits vari-
ously.
THR1 : PT=set value, vL,
vb, tHr
THR2 : PT=0, F170, F172,
F173
AD1 : ACC, DEC,
AD2 : F500, F501
"E" trip
Enabled regardless of the
setting of
Enabled regardless of the
setting of
BIT0
0
0
0
0
0
0
E6581393