Emerson Rosemount 928 Reference Manual page 95

Wireless gas monitor
Hide thumbs Also See for Rosemount 928:
Table of Contents

Advertisement

Reference Manual
00809-0100-4928
5. On the Alarm Limit screen, enter a gas concentration limit to trigger the local
6. Select OK.
7. On the Local Output screen, select Alarm Latching.
8. On the Alarm Latching screen, select one of the following:
9. Select OK.
10. On the Local Output screen, select Alarm Output.
alarm.
Not Latched: If you select this option, the local alarm is not latched. This is the
default option.
Latch Conc Alarms: If you select this option, the local alarm output latches for
gas concentration alarms. Refer to
about resetting latched alarms.
Resetting latched alarms
Configuration
August 2018
for information
95