Quick Start Guide
00825-0100-4295, Rev AA
October 2018
TM
Rosemount
9295 Process Flow Meter

Advertisement

loading

Summary of Contents for Emerson Rosemount 9295

  • Page 1 Quick Start Guide 00825-0100-4295, Rev AA October 2018 Rosemount 9295 Process Flow Meter...
  • Page 2: Table Of Contents

    Quick Start Guide NOTICE This guide provides basic guidelines for the installation of the Rosemount 9295 Primary Element. For comprehensive instructions on configuration, diagnostics, maintenance, service or troubleshooting, refer to the Rosemount 9295 Primary Element Reference Manual and appropriate transmitter reference manuals. The manual and this guide are also available electronically on Emerson.com/Rosemount.
  • Page 3: Before You Begin

    J. Rod-out plug (1/2” ANPT) K. Primary element tag L. Primary element M. RTD assembly plug The four steps to install and zero the Rosemount 9295 Process Flow Meter are described in this guide: Locate the installation point Orient the primary element...
  • Page 4: Locate The Installation Point

    (2) Straight pipe lengths are measured from the upstream and downstream flanges of the Rosemount 9295 primary element. A zero diameter requirement implies that the primary element can be installed directly adjacent to a disturbance.
  • Page 5 October 2018 Reversing the electronics (transmitter and RTD) The Rosemount 9295 primary element with direct mount transmitter has reversible electronics. If there is interference in the mounting location, the transmitter and RTD (if applicable) can be reinstalled on the opposite side of the meter by following the directions below.
  • Page 6 October 2018 Quick Start Guide Table 2. Torque Values for Transmitter Mounting Bolts Bolt material Head markings Initial torque Final torque Carbon steel (CS) 300 in-lb 650 in-lb Stainless steel (SST) 150 in-lb 300 in-lb...
  • Page 7: Orient The Primary Element

    Quick Start Guide October 2018 Orient the primary element The primary element can be installed in any position around the circumference of the pipe, provided the vents are positioned within the recommended zone to allow for bleeding or venting. Orienting the unit within the recommended zone will also prevent inaccurate measurements.
  • Page 8 October 2018 Quick Start Guide Remote transmitter mount meter orientations Figure 6. Horizontal Flow Orientation Based on Fluid Type Liquids Steam Figure 7. Vertical Flow Orientation Based on Fluid Type Liquids Steam...
  • Page 9 Quick Start Guide October 2018 Redundant transmitter direct mount meter orientations Figure 8. Horizontal Flow Orientation Based on Fluid Type Liquids Steam Note For all orientations, the meter should be level with the grade. Figure 9. Vertical Flow Orientation Based on Fluid Type Liquids Steam Not permitted...
  • Page 10 October 2018 Quick Start Guide Redundant transmitter remote mount meter orientations Figure 10. Horizontal Flow Orientation Based on Fluid Type Liquids Steam Note For all orientations, the meter should be level with the grade. Figure 11. Vertical Flow Orientation Based on Fluid Type Liquids Steam...
  • Page 11: Install The Primary Element

    Quick Start Guide October 2018 Install the primary element The unit must be oriented with the flow arrow pointing in the direction of flow. Otherwise, the primary element will produce erroneous readings. See Figure Figure 12. Flow Direction 1. Lift the meter by using the straps on the body of the meter. See Figure Follow local guidelines on lifting safety.
  • Page 12 October 2018 Quick Start Guide 2. Install the flanged ends into the process pipe as shown in Figure Figure 14. Installed Meter 3. Use the appropriate studs, nuts, gaskets and torque spec for the given flange size, rating and process conditions. Tighten the nuts following a star pattern. Figure Figure 15.
  • Page 13 Quick Start Guide October 2018 For remote mount installations, use stainless steel tubing with the largest convenient internal diameter per site practices. A best practice is to minimize the length of the impulse lines. An example of a remote mount installation is shown in Figure Figure 16.
  • Page 14: Trim The Transmitter

    October 2018 Quick Start Guide Trim the transmitter Before the unit is put in service, a transmitter zero trim should be performed at normal line pressure: 1. Start the procedure by closing all the valves on the unit. 2. Open both primary isolation valves (D and G). See Figure 3.
  • Page 15: Additional Information

    Additional information Rod-out operation The Rosemount 9295 Process Flow Meter is designed to accommodate a right angle (90°) rod-out tool with 1/2” NPT connection. Straight rod-out tools may need a nipple extension installed in order to provide clearance for the transmitter housing.