9. Select OK when the zero measurement reading stabilizes.
c) Attach a length of calibration tubing (PVC tubing, 3/16-in. ID, 5/16-in. OD)
from the regulator on the clean air cylinder to the fitting on the Rosemount
628 Gas Sensor Module IP filter assembly (part number 00628-9000-0001).
d) Release the clean air to the sensor.
Note
If you need a long length of calibration tubing to reach the device, make
allowances for a delay in response time from the sensor while the clean air
travels the length of the calibration tubing.
e) Complete
Step 9
f) Complete
Step 13
g) Turn off the clean air when the sensor is correctly zeroed.
Note
Negative measurement readings may occur and are normal during zeroing.