6.10 Data for Eaton 9PX Split phase
6.10.1 Status table
Status description
Load protected
UPS coupled
Unit general alarm
Configuration firmware fault
UPS in backup
Battery low warning
Low battery
Operation on static switch
Communication fault
UPS overload
Emergency stop
Battery to be checked
Device ventilation fault
Classe d'UPS
Mode ECO = 1
Battery present
Battery test
Fuse fault
Timer expired
Mains 1 voltage out of tolerance
Mains 1 fuse fault
Mains 1 frequency out of tolerance
Mains 2 overload
Mains 2 thermal overload
Output on bypass
Mains 2 frequency out of tolerance
Mains 2 voltage out of tolerance
Charger general fault
Battery charge
Chopper fault
Rectifier short circuit
Inverter major fault
Inverter overload
– User Manual
Modbus MS Card
Status to 0
no
no
no
no
no
no
no
no
absent
no
absent
no
no
001 : off line / line interactive
011 : on line - unitary/parallel
100 : on line – parallel with
NS
101 : on line – hot standby
redundancy
no
absent
no
absent
absent
no
no
no
no
no
no
no
no
no
no
absent
absent
no
no
34009048XT_EN/AD
Status to 1
Word (hex)
yes
40
yes
40
yes
40
yes
40
yes
40
yes
40
yes
40
yes
40
present
40
yes
40
present
40
yes
40
yes
40
41
yes
41
present
42
yes
42
present
42
present
43
yes
44
yes
44
yes
44
yes
46
yes
46
yes
46
yes
46
yes
46
yes
49
yes
49
present
4A
present
4A
yes
4C
yes
4C
Bit
0
1
2
3
4
5
6
7
9
A
B
D
E
1 to 3
7
0
2
B
3
8
9
B
5
6
7
9
A
0
1 & 3
1
2
1
2
Page
45/55
Need help?
Do you have a question about the Modbus MS Card and is the answer not in the manual?
Questions and answers