WEBs CIPer MODEL 50 – USER GUIDE
Panel-Bus Communication tuning
The default polling time for all Panel-Bus points is set to "Normal = 10s".
This means that the data from the field are updated every 10s.
Write commands are sent without time delay.
The polling frequency can be changed, and we do recommend that it must be updated more frequently.
Important: For CIPer Model 50, the fastest poll rate is 200 milliseconds.
Do NOT set a faster poll-rate, as this may overload the CPU in larger systems.
Editing the standard polling frequency can be done inside the "Poll Scheduler" of the Property
Sheet of the PanelbusNetwork: