Power Connections; Communication Connections - Honeywell Air Alert 96d User Manual

Table of Contents

Advertisement

Available languages

Available languages

 
Topic 
J22 Power Input
 
J23, J24 Communi‐
cation inputs 
Relay Outputs 1‐4 
SHDN jumper 
EOL Resistors 1‐4 
 
Power Connections 
The controller requires a power range of 17‐27 Vac, 50/60 Hz (8.64 
VA), 18‐36 Vdc, 350 mA @24 Vdc (8.4 VA).  Polarization is not im‐
portant in either AC or DC mode.  The system must be grounded on 
the transformer and a dedicated circuit breaker must be used.
 
Communication Connections 
Communication cables must be grounded using the shield terminal, 
using twisted and shielded pair Belden 2‐24 AWG #9841 cable (or 
equivalent). 
The network cabling can extend up to 2000 feet (609 m) per channel. 
Daisy‐chain the network cable with no T‐taps. 
 
Connect the power supply to the controller (see 
Wiring Details for cabling diagrams)
Connect communication cables to channels 1 
through 3.   
Depending on the desired configuration, con‐
nect the relay cables to either N.O. or N.C. Re‐
lays 1 and 2 are commandable by either inter‐
nal events or by BACnet; relays 3 and 4 are 
driven only by internal events. 
Place the jumper over the Shutdown header 
pins to reset or restart the system. 
Place the jumper over the header pins to in‐
clude resistors to attenuate communication 
echoes. 