Description of the XCL8010AU Controller Module

XCL8010AU, I/O Modules on Single Rail

Connect XCL8010AU Controller Module and I/O modules
using the bridge connectors.
This provides power supply and communication connection.
No further wiring is necessary.

Multiple Rails in Single Cabinet

The multiple rails of a controller system are connected in
series.
Connect the rail ends as follows:
– Power supply
via power supply terminals 73, 74 or 77, 78
– Communication
via communication terminals 71, 72 or 75, 76
71
72
I/O MODULE
73
74
71
72
I/O MODULE
73
74
71
72
I/O MODULE
73
74
71
72
I/O MODULE
73
74
Fig. 10. Wiring the power supply and the communication
lines to the I/O modules

LonWorks Bus I/O Modules in Separate Rooms

In this scenario, only communication lines must be connected
between the rooms.
Connect the last module of room 1 to the first module of
room 2:
– via communication terminals 71, 72 or 75, 76
EN1B-0410GE51 R0908A
75
76
I/O MODULE
I/O MODULE
77
78
75
76
XCL8010AU
I/O MODULE
77
1 2
78
ROOM 1
71
72
LonWorks
73
I/O MODULE
74
ROOM 2
LonWorks
73
I/O MODULE
74
Fig. 11. Wiring the L
separate rooms
Maximum Cable Length
Max. cable length: 1200 meters (4000 ft), supervised.

How to Connect Panel Bus and L

Bus Mixed Controller Systems

Connecting I/O Modules

For connecting the I/O modules with each other, proceed as
described for single-bus controller systems.

Connecting I/O Modules to the XCL8010AU

Panel Bus I/O Modules
Connect communication terminals 71 ─ 74 or 75 ─ 78 of
Panel Bus I/O modules to communication terminals 71 ─
74 or 75 ─ 78 of the XCL8010AU Controller Module using
either
– Bridge connectors
for flush mounting on a single DIN rail or
– Cables
for separate mounting, e.g., on multiple rails, separate
cabinets, etc.
L
W
Bus I/O Modules
ON
ORKS
Connect communication terminals 71 ─ 74 or 75 ─ 78 of
L
W
Bus I/O modules to L
ON
ORKS
14 of the XCL8010AU using cables.
12
75
76
LonWorks
XCL8010AU
77
I/O MODULE
1 2
78
75
76
LonWorks
LonWorks
I/O MODULE
I/O MODULE
77
78
W
Bus I/O modules in
ON
ORKS
W
ON
W
terminals 11 ─
ON
ORKS
Excel 800
ORKS