Panel-Bus Cable Type And Length - Honeywell CIPer 50 User Manual

Table of Contents

Advertisement

CIPer
MODEL 50 CONTROLLER – USER GUIDE
TM
The Assignment of the different Poll Intervals for each point is done inside the Panelbus Point Discovery Dialog.

Panel-Bus cable type and length

See CIPer Model 50 Installation and Commissioning Instructions – 31- 00233 for all details.
Max. Panel Bus length:
120 ft (36.5 m) for any type of cabling and topology. No additional end termination is permitted.
2400 ft (731.5m) for twisted-pair or telephone cable and daisy chain topology. The Controller must be positioned
at one end of the Panel-Bus, and an end termination (120 Ω) at the other end. Furthermore, the three-position
slide switch must be set to "END." Use Honeywell cable 3322 or 3251.
25
31-00198-03