EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Tuning Panel Bus Communication

The default polling interval for all Panel Bus points is set to "normal = 10s". Data from the field is thus updated every 10s.
Write commands are sent without time delay.
It is recommended that you update the polling interval of those points requiring more-frequent updating (see Fig. 40).
IMPORTANT
For EAGLEHAWK NX, the fastest poll rate is 200 milliseconds.
Do NOT set a faster poll rate, as this may overload the CPU in larger systems.
Fig. 40. Editing the standard polling interval in "Poll Scheduler" of Property Sheet of PanelbusNetwork