Power Unit Consumption - Paradox Digiplex DGP-848 Programming Manual

Security and access control
Hide thumbs Also See for Digiplex DGP-848:
Table of Contents

Advertisement

Description
Grafica Graphic LCD Keypads (DNE-K07):
LCD Keypads (DGP2-641):
LED Keypads (DGP2-648):
Motion Detector Modules (DGP2-50/60/70):
Door Contact Modules (DGP2-ZC1):
1-Zone Expansion Modules (DGP2-ZX1):
4-Zone Expansion Modules (APR3-ZX4):
8-Zone Expansion Modules (APR3-ZX8):
Omnia Wireless Expansion Modules (OMN-RCV3):
1-PGM Expansion Modules (APR3-PGM1):
4-PGM Expansion Modules (APR3-PGM4):
Printer Modules (APR3-PRT1):
DVACS Module (DGP2-DVAC):
InTouch Voice-Assisted Arm/Disarm Modules (APR3-ADM2):
Access Control Module (DGP2-ACM1P):
Note: The DGP2-ACM1P consumes 165PU from its own power supply.
Other devices such as hardwired motion detectors (1mA = 1PU)
Maximum available power units = 700PU
1. Using Table 3, calculate the total number of power units (PU) required by each device, module, and accessory in the
system. Please take into account devices connected to the control panel's PGM outputs. Since the
own power supply, do not include the sirens connected to it in the calculation.
2. If the Grand Total is less than 700PU, go to step 3. If the value is greater, you will require an external power supply (see
External Power Supply on page 44) to provide the additional power needed. Proceed with step 3.
3. Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only
a specific number of power units (PU). Using Table 4, determine how many power units each length of wire can support.
Please note that the total number of power units (PU) can never surpass 700PU.
Gauge: 18AWG Surface: 0.823mm
Length of each
Available Power
run of wire
Units (PU)
100ft. (30m)
200ft. (61m)
300ft. (91m)
400ft. (122m)
500ft. (152m)
600ft. (183m)
700ft. (213m)
800ft. (244m)
900ft. (274m)
1000ft. (305m)
1500ft. (457m)
2000ft. (610m)
2500ft. (762m)
3000ft. (914m)

Power Unit Consumption

Table 3: Power Unit Consumption Table
Table 4: Power Unit (PU) Limitations For Each Run of Wire
Gauge: 22AWG Surface: 0.326mm
2
Length of each
run of wire
700
100ft. (30m)
700
200ft. (61m)
700
300ft. (91m)
700
400ft. (122m)
690
500ft. (152m)
575
600ft. (183m)
493
700ft. (213m)
431
800ft. (244m)
383
900ft. (274m)
345
1000ft. (305m)
230
172
138
115
Digiplex DGP-848
QTY.
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
GRAND TOTAL
Gauge: 24AWG Surface: 0.205mm
2
Available Power
Units (PU)
700
682
454
341
273
227
195
170
151
136
- 42 -
Programming Guide
PU used by each
130PU =
__________ PU
60PU =
__________ PU
45PU =
__________ PU
16PU =
__________ PU
14PU =
__________ PU
15PU =
__________ PU
20PU =
__________ PU
40PU =
__________ PU
50PU =
__________ PU
50PU =
__________ PU
150PU =
__________ PU
40PU =
__________ PU
40PU =
__________ PU
70PU =
__________ PU
165PU =
__________ PU
__________ PU
__________ PU
BELL
Length of each
Available Power
run of wire
Units (PU)
100ft. (30m)
200ft. (61m)
300ft. (91m)
400ft. (122m)
500ft. (152m)
600ft. (183m)
Total PU
output has its
2
700
429
286
214
171
143

Hide quick links: