Connecting Fire Circuits

For 4-wire installation, program the activation event so that the smoke detectors can be reset by simultaneously pressing
event group 06 on page 21). For 2-wire installation, press
SP65).
WARNING: It is recommended that smoke detectors be connected in a daisy-chain configuration. Each control panel, except for the SP4000, SP5500, and
SP65, supports a maximum of five 2-wire smoke detectors.

Alarm Relay and PGM Connections

AC Power & Backup Battery Connections
WARNING: A 12 Vdc / 7 Ah battery is required to comply with UL fire
requirements.
WARNING: Improper connection of the transformer may result in
damage to the system.
WARNING: Disconnect battery before replacing the fuse.

Demonstration or Emergency System Power-up without an AC Source

To power-up the control panel for demonstration or emergency purposes only, use a standard 12 VDC, 4 Ah/7 Ah backup battery. To power the control panel using
a backup battery:
1.
Connect the battery to the control panel's
2.
Use a wire to short the battery's negative terminal to the panel's
and
simultaneously to automatically reset smoke detectors (not applicable to SP5500, SP4000,
CLEAR
ENTER
terminal.
BATT
- terminal.
AUX
Table 56: PGM power sources
Power Source
Description
AUX + terminal
MG5000/MG5050: max. 700 mA
SP5500/SP6000/SP7000: max. 700 mA
SP4000: max. 600 mA
SP65: max. 750 mA
External power supply
PGMs cannot exceed 100 mA or the power supply's
current limit.
Table 57: Transformation requirements
Power Source
Description
Transformer
16 Vac 20 VA* (Amseco XP-1620)
16.5 Vac 40 VA (Universal UB1640W)
* not verified by UL
DC power supply rate •
MG5000/MG5050: 1.0A
SP5500/SP6000/SP7000: 1.4A
SP4000/SP65: 1.1A
Auxiliary supply rate
MG5000/MG5050: typ. 600 mA / max. 700 mA
SP5500/SP6000/SP7000: typ. 600 mA / max.
700 mA
SP4000: typ. 450 mA / max. 600 mA
SP65: typ. 500 mA / max. 750 mA
UL installations: typ. 200 mA
Acceptable battery
MG5000/MG5050: 350 mA / 700 mA
charge current
SP5500/SP6000/SP7000: 350 mA / 700 mA
(see section [700],
SP4000/SP65: 1.1A
option 2, on page 37)
and
for three seconds (see
CLEAR
ENTER
59