Operating hours counter
8.2 Preset and apply start values for operating hours counters
Structure of data record DS 143
The following overview shows the structure of the data record DS 143 in simplified form.
More detailed information about the structure of data record 143 is available in section
Structure for energy counters (DS 143) (Page 232).
Byte
0
1
2
3
4
5
6
7
8...15
16...23
:
158...161
162...165
166...169
Assignment of data record DS 143
Byte 0 and Byte 1: Version of the data record
Header information for the version of the data record.
Byte 2 ... Byte 7: Control bytes for energy and overflow counter
When data record 143 is written with the WRREC instruction, Bytes 2 to 7 are used as
phase-specific control information for energy meters, overflow counters and operating hours
counters. The length of the control information amounts to 2 bytes for each phase.
Byte 8 ... byte 157: Start values for the individual energy meters and overflow counters
The start values for energy counters in data record 143 are 64-bit floating point numbers.
The format corresponds to the data type LREAL in S7-1200 and in S7-1500.
The initial values for overflow counters in data record 143 are 16-bit integers. The format
corresponds to the data type UINT in S7-1200 and in S7-1500.
Byte 158 ... byte 169: Start values for operating hours counter
The start values for operating hours counters in data record 143 are 32-bit integers. The
format corresponds to the data type REAL in S7-1200 and in S7-1500.
72
Measured variable
Version
Reserved
Control byte 1 - L1
Control byte 2 - L1
Control byte 1 - L2
Control byte 2 - L2
Control byte 1 - L3
Control byte 2 - L3
Start value for active en-
ergy inflow L1
Initial value active energy
outflow L1
:
Start value operating
hours L1
Start value operating
hours L2
Start value operating
hours L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Data
Unit
Value range
type
BYTE
-
1
BYTE
-
0
BYTE
Bit string
-
BYTE
Bit string
BYTE
Bit string
BYTE
Bit string
BYTE
Bit string
BYTE
Bit string
LREAL Wh
LREAL Wh
You will find the exact
assignment in the section
Structure for energy coun-
:
:
ters (DS 143) (Page 232).
REAL
h
REAL
h
REAL
h
Measured
value ID
-
-
-
61180
61181
:
65505
65506
65507