Article number
Accuracy class according to IEC 61557-12
–
Measured variable voltage
–
Measured variable current
–
Measured variable apparent power
–
Measured variable active power
–
Measured variable reactive power
–
Measured variable power factor
–
Measured variable active energy
–
Measured variable reactive energy
–
Measured variable neutral current
–
Measured variable phase angle
–
Measured variable frequency
–
Measured variable harmonic
–
Measured variable THDU
–
Measured variable THDI
Accuracy class line analysis acc. to IEC 61000-4-
30
–
Measured variable voltage
–
Measured variable current
–
Measured variable frequency
–
Measured variable voltage interruption
–
Measured variable voltage dip and
swell
–
Measured variable harmonic voltage
–
Measured variable harmonic current
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
Between the channels and load voltage L+
•
Isolation
Isolation tested with
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
6ES7134-6PA00-0CU0
0,2
0,2
0.5
0.5
1
0.5
0.5
1
0,2
±0.5 °; not covered by IEC 61557-12
0.05
1
1
1
Class S
Class S
Class S
Class S
Class S
Class S
Class S
No
Yes
Yes; Including FE
Between channels and backplane bus, 24 V
supply: Routine test, 1 920 V AC, 2 s; between
backplane bus and 24 V supply: Type test, 707 V
DC
Technical specifications
15.1 Technical specifications
137