Siemens Simatic ET 200SP Manual page 205

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Module versions
C.4 Module version "EE@Industry measurement data profile E0 / E1 / E2 / E3"
Table C- 8
Byte
0...3
4...7
8...11
Table C- 9
Byte
0...3
4...7
8...11
12...15
16...19
20...23
24...31
32...39
40...47
48...55
56...59
60...63
64...67
68...71
72...75
76...79
80...83
84...87
88...91
92...95
96...99
100...10
3
Structure of output user data
The structure of the 20-byte output user data is fixed and is identical to the output user data
(control bytes) of the Module version "32 I / 20 Q" (Page 195).
204
Measurement data profile E2
Allocation
Total active power L1L2L3
Total active energy L1L2L3 inflow
Total active energy L1L2L3 outflow
Measurement data profile E3
Allocation
Active power L1
Active power L2
Active power L3
Reactive power Qtot L1
Reactive power Qtot L2
Reactive power Qtot L3
Total active energy L1L2L3 inflow
Total active energy L1L2L3 outflow
Total reactive energy L1L2L3 inflow
Total reactive energy L1L2L3 outflow
Voltage UL1-N
Voltage UL2-N
Voltage UL3-N
Voltage UL1-UL2
Voltage UL2-UL3
Voltage UL3-UL1
Current L1
Current L2
Current L3
Power factor L1
Power factor L2
Power factor L3
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Data
Unit
Value range
type
REAL
1 W
-3.0e+9 ... +3.0e+9
REAL
1 Wh
0.0 ... 3.4028e+38
REAL
1 Wh
0.0 ... 3.4028e+38
Data
Unit
Value range
type
REAL
1 W
-3.0e+9 ... +3.0e+9
REAL
1 W
-3.0e+9 ... +3.0e+9
REAL
1 W
-3.0e+9 ... +3.0e+9
REAL
1 var
-3.0e+9 ... +3.0e+9
REAL
1 var
-3.0e+9 ... +3.0e+9
REAL
1 var
-3.0e+9 ... +3.0e+9
LREAL 1 Wh
0.0 ... 1.7976e+308
LREAL 1 Wh
0.0 ... 1.7976e+308
LREAL 1 varh 0.0 ... 1.7976e+308
LREAL 1 varh 0.0 ... 1.7976e+308
REAL
1 V
0.0 ... 1000000.0
REAL
1 V
0.0 ... 1000000.0
REAL
1 V
0.0 ... 1000000.0
REAL
1 V
0.0 ... 1000000.0
REAL
1 V
0.0 ... 1000000.0
REAL
1 V
0.0 ... 1000000.0
REAL
1 A
0.0 ... 100000.0
REAL
1 A
0.0 ... 100000.0
REAL
1 A
0.0 ... 100000.0
REAL
-
0.0 ... 1.0
REAL
-
0.0 ... 1.0
REAL
-
0.0 ... 1.0
Manual, 07/2018, A5E42674880-AA
Mea
sure
d
value
ID
34
200
201
Mea
sure
d
value
ID
13
14
15
22
23
24
210
211
212
213
1
2
3
4
5
6
7
8
9
19
20
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents