Siemens Simatic ET 200SP Manual page 160

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 130/131.
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
Measured variables for user data mapping
You can find the measured variables under Measured variables (Page 163). The following
measured variables are not available to you for user data mapping:
● 220 to 226
● 62110 to 62116
● 62210 to 62216
● 62310 to 62316
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
A.4 Structure of the parameter data records 130/131 for user-data mapping
Meaning
Byte 3
00
Number of the data record unknown
01
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Incorrect version
02
Error in the header information
01
Reserved bits are not 0.
21
"User data variant" not possible or input
data configuration not large enough
30
Data record number invalid
31
"Length of the parameter block" invalid.
32
"Number of parameter blocks" invalid.
33
"ID of the measured value for limit monitor-
ing" invalid.
3B
"ID of the type of user data mapping" not
permitted.
Parameter data records
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the station whether the mod-
ule is plugged or drawn.
Check the assigned values for the
parameters of the WRREC instruction
Check Byte 0. Enter valid values.
Check Bytes 1 and 2. Correct the
length and number of the parameter
blocks.
Check Byte 3 and set reserved bits
back to 0.
Select a different user data variant or
change the configuration.
Check the data record number. Enter
a valid data record number.
Check Byte 1. Length = 10 bytes
Check Byte 2. Enter valid values.
Check Bytes 4 and 5. Enter valid
values.
Check Byte 1. Number for user-
specific user data variant has to be
01
or 02
.
H
H
159

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents