Parameter data records
A.5 Structure of the parameter data record 135 for data record mapping
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 130/131/135.
Error code in STATUS parameter
(hexadecimal)
Byte 0
Byte 1
Byte 2
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
Measured variables for data record mapping
You can find the measured variables under Measured variables (Page 163). The following
measured variables are not available to you for data record mapping:
● 220 to 226
● 62110 to 62116
● 62210 to 62216
● 62310 to 62316
162
Meaning
Byte 3
00
Number of the data record unknown
01
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Incorrect version
02
Error in the header information
01
Reserved bits are not 0.
21
"User data variant" not possible or input
data configuration not large enough
30
Data record number invalid
31
"Length of the parameter block" invalid.
32
"Number of parameter blocks" invalid.
33
"ID of the measured value for limit monitor-
ing" invalid.
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the station whether the mod-
ule is plugged or drawn.
Check the assigned values for the
parameters of the WRREC instruction
Check Byte 0. Enter valid values.
Check Bytes 1 and 2. Correct the
length and number of the parameter
blocks.
Check Byte 3 and set reserved bits
back to 0.
Select a different user data variant or
change the configuration.
Check the data record number. Enter
a valid data record number.
Check Byte 1. Length = 10 bytes
Check Byte 2. Enter valid values.
Check Bytes 4 and 5. Enter valid
values.