Siemens Simatic ET 200SP Manual page 113

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Interrupts/diagnostic alarms
14.3 Diagnostic alarms
Table 14- 5
Error types
Diagnostic message
Undervoltage
Overvoltage
Overload
Error
Parameter assignment
error
Load voltage missing
External fault
Channel is temporarily
unavailable
112
Error code
Meaning
2
Line voltage (measuring range) is moni-
H
tored for tolerance. Violation leads to volt-
3
H
age overflow/underflow
4
The measured current is monitored
H
after the "Tolerance time" for "Toler-
ance value overcurrent [0.1A]" has ex-
pired. Exceeding this results in
overflow current.
The maximum value of the secondary
current (12 A) has been exceeded.
9
Internal module error (diagnostic alarm on
H
channel 0 applies to the entire module).
10
The module cannot evaluate parame-
H
ters for the channel.
Incorrect parameter assignment.
11
Missing or insufficient line voltage at termi-
H
nal 17
1A
Voltage swell/dip and overcurrent
H
1F
Firmware upgrade is being performed.
H
Channel 0 applies to the entire module.
The module is currently not performing any
measurements.
A user calibration is being executed at the
channel.
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Solution
Observe the line voltage range
Observe the current range
Replace the module
Correct the parameter assignment
Check supply
see:
Voltage swell of the voltage half-
wave value (Page 116)
Voltage dip of the voltage half-
wave value (Page 118)
Overcurrent of the current half
value (Page 129)
--
Complete the user calibration
Manual, 07/2018, A5E42674880-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents