Quick Start - Siemens Simatic ET 200SP Manual

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Quick start

Introduction
This section shows you how to read and view your first measured values on the
AI Energy Meter HF in a particularly quick and easy way.
Requirement
You have already connected the AI Energy Meter HF to your network with one of the
connection types shown in the section Wiring (Page 20). The AI Energy Meter HF has
already been integrated in your configuration tool (such as STEP 7), or the AI Energy Meter
HF has been integrated in your hardware catalog of your configuration tool with the GSD file.
Procedure
1. Configure an ET 200SP station
Configure an ET 200SP station with a CPU 151xSP or an IM 155-6.
2. Plug module in ET 200S station
Plug the AI Energy Meter HF into the ET 200SP station and use the module version with
32-byte inputs and 20-byte outputs.
3. Set the module parameters
– Connection type that you have used for the AI Energy Meter HF (e.g. 3P4W)
– Voltage measuring range
– Frequency of your network (for example 50 Hz)
– Nominal value current and nominal value voltage for the phases
– Primary and secondary current of the used current transformer (e.g. 100 A and 1 A)
– Primary and secondary voltages of the used voltage transformer (e.g. 230 V and 230
Leave all other parameters at their default settings and do not change them.
4. Load configuration
Switch on the ET 200SP station and download the configuration to the CPU.
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Set the following parameters for the AI Energy Meter HF:
V)
5
39