Siemens Simatic ET 200SP Manual page 137

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Technical specifications
15.1 Technical specifications
Article number
Measuring inputs for voltage
Measurable line voltage between phase
and neutral conductor
Measurable line voltage between the
line conductors
Measurable line voltage between phase
and neutral conductor, min.
Measurable line voltage between phase
and neutral conductor, max.
Measurable line voltage between the
line conductors, min.
Measurable line voltage between the
line conductors, max.
Measurement category for voltage
measurement in accordance with IEC
61010-2-030
Internal resistance line conductor and
neutral conductor
Power consumption per phase
Impulse voltage resistance 1,2/50µs
Measuring inputs for current
measurable relative current (AC), min.
measurable relative current (AC), max.
Continuous current with AC, maximum
permissible
Apparent power consumption per
phase for measuring range 5 A
Rated value short-time withstand cur-
rent restricted to 1 s
Input resistance measuring range 0 to 5
A
Zero point suppression
Surge strength
136
6ES7134-6PA00-0CU0
300 V
519 V
3 V
300 V
6 V
519 V
CAT II
1.5 MΩ
60 mW; 300 V AC
2.5 kV
1 %; Relative to the secondary rated current 5 A
100 %; Relative to the secondary rated current 5
A
5 A; 6 A permanent thermal overload
0.6 V·A
100 A
25 mΩ; At the terminal
0 ... 20%, referred to the nominal current
10 A; for 1 minute
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA

Hide quick links:

Advertisement