Technical specifications
15.1 Technical specifications
Article number
Power loss
Power loss, typ.
Address area
Address space per module
Inputs
•
Outputs
•
Hardware configuration
Automatic encoding
Mechanical coding element
•
Selection of BaseUnit for connection variants
2-wire connection
•
Time of day
Operating hours counter
present
•
Analog inputs
Cycle time (all channels), typ.
Cable length
shielded, max.
•
unshielded, max.
•
Analog value generation for the inputs
Sampling frequency, max.
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm
•
Limit value alarm
•
Hardware interrupt
•
134
6ES7134-6PA00-0CU0
1.4 W; 4x 5 A input current, 3x 230 V AC
256 byte
20 byte
Yes
Yes
BU type U0
Yes
50 ms; Time for consistent update of all meas-
ured and calculated values (cyclic und acyclic
data)
200 m
200 m
2 048 kHz
No
Yes
Yes
Yes; Monitoring of up to 16 freely selectable
process values (exceeding or undershooting of
value)
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA