Siemens Simatic ET 200SP Manual page 100

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Parameters
Diagnostics
overflow cumulative values
Detect voltage swell and dip
Detect peak value current
Detect peak value voltage
Detect overcurrent
Analyse harmonics
Nominal value current [A]
Tolerance factor overcurrent in
relation to nominal value current
[0.1%]
Tolerance time overcurrent [ms]
Low limit current measurement
in relation to nominal value cur-
rent [0.1%]
Enable operating hours counter
Enable gate of operating hours
counter
Current transformer primary
current [A]
Current transformer secondary
current
Reverse current direction
Nominal value voltage [V]
Tolerance factor overvolt-
age/undervoltage [0.1%]
Voltage transformer primary
voltage [V]
Voltage transformer secondary
voltage [V]
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
Value range
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
0 ... 99999
10 ... 60000
0 ... 60000
0 ... 200
Disable
Enable
Disable
Enable
1 ... 99999 A
1 A
5 A
Disabled
Reverse current direction
1 ... 999999
10 ... 500
1 ... 999999 V
1 ... 500 V
13.1 Parameters
Default setting
Disable
Disable
Disable
Disable
Disable
Disable
1
100
40000
10
Disable
Disable
1 A
1 A
Disabled
230 V
100
230 V
230 V
Parameters
Reconfigu-
ration in
RUN
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents