Siemens Simatic ET 200SP Manual page 207

Analog input module ai energy meter 480vac/ct hf (6es7134-6pa00-0cu0)
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

User data variants
Total power L1L2L3 (ID 254 or FE
Table D- 2
Total power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Total active power L1L2L3
10 ... 11
Total reactive power Qtot L1L2L3
12 ... 13
Total apparent power L1L2L3
14 ... 17
Total active energy L1L2L3
18 ... 21
Total reactive energy L1L2L3
22
Reserved
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling total active power L1L2L3
28
Scaling total reactive power L1L2L3
29
Scaling total apparent power L1L2L3
30
Scaling total active energy L1L2L3
31
Scaling total reactive energy L1L2L3
206
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Data
Unit
Value range
type
BYTE
-
254 (FE
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
UINT
1 mA
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
DINT
1 Wh
-2147483647...
+2147483647
DINT
1 varh
-2147483647...
+2147483647
BYTE
-
0
USINT
0.01
0 ... 100
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
Meas-
ured
value
ID
)
-
H
-
66007
66008
66009
66034
66038
66036
225
226
-
66037
-
-
-
-
-
-
-
-
Manual, 07/2018, A5E42674880-AA