parameter descriptions
f out
f n
DC-braking ON
t = 1 x par. 4.10
RUN
STOP
Figure 9.8: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the
set deceleration parameters, if the inertia of the motor and load allows that,
to the speed defined with parameter 4.11, where the DC-braking starts.
The braking time is defined with parameter 4.10. See Figure 9.9.
Par. 4.1
Figure 9.9: DC-braking time when Stop mode = Ramp
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
Output frequency
Motor speed
0,1 x f n
t
f out
1
RUN
STOP
f out
f n
Output frequency
Motor speed
DC-braking ON
t = 0,1 x par. 4.10
RUN
STOP
Motor speed
Output frequ ency
DC-braking
t
t = par. 4.
10
vacon
77
t
9