Summary of Contents for Vacon 10

  • Page 1 ® ac drives quick guide...
  • Page 3 The motor terminals U, V, W (T1, T2, T3) and the possible brake resistor terminals - / + are live when Vacon 10 is connected to mains, even if the motor is not running. The control I / O-terminals are isolated from the mains poten- tial.
  • Page 4 • vacon safety Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 5: Mechanical Installation

    • installation vacon 2. INSTALLATION 2.1 Mechanical installation There are two possible ways to mount Vacon 10 in the wall. either screw or DIN-rail mounting. BACK BACK BACK RESET RESET RESET Figure 2.1: Screw mounting, MI1 - MI3 Figure 2.2: DIN-rail mounting, MI1 - MI3 Note! See the mounting dimensions on the back of the drive.
  • Page 6 • vacon installation Attach the support AFTER installing the power cables Attach this plate BEFORE installing the power cables Figure 2.3: Attaching the PE-plate and API cable support, MI1 - MI3 Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 7: Cabling And Connections

    Mot or out L1 L2/N L3 R+ R- U/ T1 V/T2 W/T3 Strip the plastic cable coating for 360° earthing BRAKE MOTOR MAINS RESISTOR Figure 2.5: Vacon 10 power connections, MI2 - MI3 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 8: Control Cabling

    • vacon installation 2.2.2 Control cabling Figure 2.6: Open the lid MI1 - MI3 Control cable tightening torque: 0.4 Nm Strip the plastic cable coating for 360°earthing Figure 2.7: Install the control cables, MI1 - MI3 Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 9: Control I / O And Terminals

    250Vac/2A or 250Vdc/ 25 RO 21 0,4A 26 RO 24 Table 3.1: Vacon 10 default I/O configuration and connections P) = Programmable function, see parameter lists and descriptions, chapters 5. Figure 3.1: Vacon 10 I / O 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 10 • vacon vacon 10 api Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 11: Navigation & Startup

    • navigation & startup vacon 4. NAVIGATION & STARTUP 4. 1 The main menus of Vacon 10 R E A D Y R U N S T OP A L A R M FA U LT R E A D Y...
  • Page 12: Commissioning Steps

    Table 4.1: Commissioning steps 4.2.2 Startup wizard Vacon 10 runs the startup wizard in first power-up. The wizard can be run by setting SYS Par.4.2 =1. The following figures show the procedure. NOTE! Running the startup wizard will always return all parameter...
  • Page 13 P4.2 Acc. time (s) P2.2 Start function P4.3 Dec time (s) READ Y RUN STOP ALARM FAU LT FWD REV I/O KEY PAD BUS Press OK to confirm drive setup Figure 4.3: Drive setup 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 14 • vacon navigation & startup Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 15: Monitoring & Parameters

    • monitoring & parameters vacon 5. MONITORING & PARAMETERS NOTE! This guide is for Vacon 10 standard application, if you need description of parameters in detail, please download the application manual on: www.vacon.com -> downloads. 5.1 Monitoring values Code Monitoring signal...
  • Page 16 Activated by digital P3.4 Preset speed 0 P3.1 P3.2 5,00 inputs Activated by digital P3.5 Preset speed 1 P3.1 P3.2 10,00 inputs Activated by digital P3.6 Preset speed 2 P3.1 P3.2 15,00 inputs Activated by digital P3.7 Preset speed 3 P3.1...
  • Page 17 0 = Disable Automatic reset P14.1 1 = Enable 0 = All parameters visi- Parameter P17.2 conceal 1 = Only quick setup parameter group visible Table 5.2: Quick setup parameters 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 18 Field weakening point fre- 320,00 8,00 P1.10 point 60,00 quency Voltage at field weakening Field weakening 10,00 200,00 100,00 P1.11 point as % of U point voltage nmot U / f mid point 50,00 / Mid point frequency for 0,00 P1.10...
  • Page 19 B11 = Low noise B12 = Dead time compen- sation* B13 = Flux error compen- sation* *Enable by default Table 5.3: Motor settings NOTE! These parameters are shown, when P17.2 = 0. 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 20 P3.4 Preset speed 0 P3.1 P3.2 5,00 180 Activated by digital inputs P3.5 Preset speed 1 P3.1 P3.2 10,00 105 Activated by digital inputs P3.6 Preset speed 2 P3.1 P3.2 15,00 106 Activated by digital inputs P3.7 Preset speed 3 P3.1...
  • Page 21 Stop DC current 0,10 10,00 1,50 which the DC-braking is P4.11 frequency applied Start DC current 0,00 600,00 0,00 516 0 = Not active P4.12 time Table 5.6: Ramps and brakes setup 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 22 5.8 Analogue inputs (Control panel: Menu PAR -> P6) Code Parameter Unit Default Note 0 = 0 - 100% ( 0 - 10 V) P6.1 AI1 Signal range 1 = 20% - 100% ( 2 - 10 V) P6.2 AI1 Custom min...
  • Page 23 0 = No inversion P8.4 RO2 inversion 1588 1 = Inverted Table 5.9: Digital outputs 5.10 Analogue outputs (Control panel: Menu PAR -> P9) Code Parameter Unit Default ID Selections 0 = Not used 1 = Output freq. (0-f...
  • Page 24 Mtp:Zero speed cooling 150,0 40,0 706 Cooling as % at 0 speed P13.9 Mtp:Thermal time Motor thermal time con- P13.10 constant stant FWD/REV conflict 1463 Same as P13.1 P13.23 supervision Table 5.11: Protections NOTE! These parameters are shown, when P17.2 = 0.
  • Page 25 3 = High Torque NOTE! Visible only when Startup wizard is active 0 = All parameters visible Parameter P17.2 1 = Only quick setup conceal parameter group visible Table 5.14: Application Setting parameters 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 26: System Parameters

    • vacon monitoring & parameters 5.15 System parameters Code Parameter Min Max Default Note Software information (MENU PAR -> V1) V1.1 API SW ID 2314 V1.2 API SW version V1.3 Power SW ID 2315 V1.4 Power SW version V1.5 Application ID V1.6...
  • Page 27 V3.5 Run counter: Hours V3.6 Fault counter 1 = Restores factory Restore factory defaults defaults for all P4.2 parameters F5.x Active Fault menu F6.x Fault History menu Table 5.15: System parameters 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 28 • vacon monitoring & parameters Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 29: Fault Tracing

    Application fault Output phase fault IGBT Overtemperature Analog input select 20% - Frequency converter 100% (selected signal range undertemperature 4 to 20 mA or 2 to 10 V) Frequency converter over- External fault temperature Motor stalled Fieldbus fault Motor overtemperature...
  • Page 30 • vacon FAULT TRACING Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 31: General Data

    Output current (depends on the unit size), overload 1.5 x I max. 1 min / 10 min -10 °C (no frost)…+40 / 50 °C (depends on the unit size): rated load- ability I Ambient operat- ing temperature Side by side installation for MI1-3 it is always 40 °C; For IP21/ Nema1 option in MI1-3 the maximum temparture is also 40 °C...
  • Page 32 - These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. - To fulfil standard EN61800-5-1, the protective conductor should be at least 10 mm Cu or 16 mm Al. Another possibility is to use an additional protective conductor of at least the same size as the original one.
  • Page 33 0.55 0004 0.75 0005 0007* 10.5 0011* 16.5 13.4 0.99 Table 7.2: Vacon 10 power ratings, 208 - 240 V, 3~ *The maximum ambient operating temperature of this drive is +40°C! 24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com...
  • Page 34 0.55 0002 0.75 0.55 0.55 0003 0.75 0.55 0004 0005 0006 0008 11.4 0,99 0009 13.5 11.5 0.99 0012 14.,9 0.99 Table 7.4: Vacon 10 power ratings, 380 - 480 V Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 35 0009 13,5 10,4 0,99 Table 7.5: Vacon 10 power ratings, 575 V Note: The input currents are calculated values with 100 kVA line transformer supply. Quick Modbus setup A: Select Fieldbus as remote control place: P2.1 to1 – Fieldbus B: Set Modbus RTU protocol to “ON”: S2.2 to 1 – Modbus A.
  • Page 36 • vacon general data Tel. +358 (0)201 2121 • Fax +358 (0)201 212205...
  • Page 38 Find your nearest Vacon office on the Internet at: www.vacon.com Manual authoring: documentation@vacon.com Document ID: Vacon Plc. Runsorintie 7 65380 Vaasa Finland Subject to change without prior notice © 2013 Vacon Plc. Rev. E1...