parameters
Code
Parameter
Acceleration time
P4.2
1
Deceleration time
P4.3
1
P6.1
AI1 Signal range
P6.5
AI2 Signal range
Automatic reset
P14.1
Parameter
P17.2
conceal
Table 8.1: Quick setup parameters
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
Min
Max
Unit
Default
0,1
3000,0
s
0,1
3000,0
s
0
1
0
1
0
1
0
1
vacon
ID
Acceleration time from
3,0
103
0 Hz to maximum fre-
quency.
Deceleration time from
3,0
104
maximum frequency to
0 Hz.
0 = 0 - 100%
1 = 20% - 100%
0
379
20% is the same as 2 V
minimum signal level.
0 = 0 - 100%
1 = 20% - 100%
0
390
20% is the same as 4
mA minimum signal
level.
0 = Disable
0
731
1 = Enable
0 = All parameters visi-
ble
1
115
1 = Only quick setup
parameter group visible
51
Note