Vacon 10 Complete User's Manual page 30

Frequency converter
Hide thumbs Also See for 10:
Table of Contents

Advertisement

installation
Fuse
Frame
Type
[A]
MI1
0001-0003
MI2
0004-0006
MI3
0008-0012
Table 3.8: Cable and fuse sizes for Vacon 10, 380 - 480 V, 3~
Fuse
Frame
Type
[A]
MI3
0002-0004
MI3
0005-0006
MI3
0009
Table 3.9: Cable and fuse sizes for Vacon 10, 575 V
Note! To fulfil standard EN61800-5-1, the protective co nductor should be at least
2
10 mm
Cu or 16 mm
ductor of at least the same size as the original one.
24-hour support (0)201 212 575 • Email: vacon@vacon.com
Mains
Motor
cable
cable
Cu
Cu [mm
2
[mm
]
6
3*1.5+1.5
3*1.5+1.5
10
3*1.5+1.5
3*1.5+1.5
20
3*2.5+2.5
3*2.5+2.5
Mains
Motor
cable
cable
Cu
Cu [mm
2
[mm
]
6
3*1.5+1.5
3*1.5+1.5
10
3*1.5+1.5
3*1.5+1.5
20
3*2.5+2.5
3*2.5+2.5
2
Al. Another possibility is to use an additional protective con-
Terminal cable size (min/max)
Main
Earth
terminal
terminal
2
]
2
2
[mm
]
[mm
]
1.5-4
1.5-4
1.5-4
1.5-4
1.5-6
1.5-6
Terminal cable size (min/max)
Main
Earth
terminal
terminal
2
]
2
2
[mm
]
[mm
]
1.5-4
1.5-4
1.5-4
1.5-4
1.5-6
1.5-6
vacon
27
Control
Relay
terminal
terminal
2
2
[mm
]
[mm
]
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
Control
Relay
terminal
terminal
2
2
[mm
]
[mm
]
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
0.5-1.5
3