2.4
I / O
Values 0...3 offer possibilities to control the starting and stopping of the AC
drive with digital signal connected to digital inputs. CS = Control signal.
The selections including the text 'edge' shall be used to exclude the possibility
of an unintentional start when, for example, power is connected, re-connected
after a power failure, after a fault reset, after the drive is stopped by Run En-
able (Run Enable = False) or when the control place is changed to I / O control.
The Start / Stop contact must be opened before the motor can be started.
Accurate stop mode is that the stop time is fixed from falling edge of DI to mo-
tor stop.
Selection
Selection name
number
CS1:Forward
0
CS2:Backward
FWD
Set
frequency
0 Hz
Set
frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad
start button
Keypad
stop button
Figure 9.3: Start/Stop logic, selection 0
9
1 = Ramping
After the Stop command, the speed of the motor is decelerated ac-
cording to the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an exter-
nal braking resistor for to be able to decelerate the motor in accepta-
ble time.
START STOP LOGIC
Note
The functions take place when the contacts are closed.
Output
frequency
1
2
3
4
parameter descriptions
10
5
6
7
8
9