Connecting Power to the Voltage/Current Connections, continued
To reduce the risk of fire, electric shock, or physical injury, it is strongly recommended
WARNING
that connections be made with all circuits de-energized and current carrying conductors
fused. If it is necessary to make connections on energized circuits, these must be
performed by Qualified Personnel ONLY with proper Personal Protective Equipment.
To avoid the risk of electric shock or burns, always connect the safety (or earth)
WARNING
ground before making any other connections.
To reduce the risk of fire, electrical shock, or physical injury it is strongly
WARNING
recommended to fuse the voltage measurement inputs.
Fuses must be located as close to the load as possible to maximize protection.
For continued protection against risk of fire or shock hazard replace only with
WARNING
same type and rating of recommended fuse.
Use only fast blow type fuse which is rated 600V. Recommended fuse type is
Littelfuse, part number KLKD.300 rated 600V AC/DC, 0.3A fast blow.
Do not replace fuse again if failure is repeated. Repeated failure indicates a
WARNING
defective condition that will not clear with replacement of the fuse. Refer
condition to a qualified technician.
3-4