Outputs

The C1000 Basic Rooftop controller contains 5 customizable outputs, 4 being Triac type switch outputs
and one being 0-10Vdc analog modulating / pulsed / On-or-Off output. Some outputs are configurable
and follow a proportional and integral algorithm (PI) to ensure precise adjustment of the device. All
configurations are performed via the ProLon Focus software.
An integrated resettable fuse protects each of the outputs of the C1000 against current surges and
short circuits. This protection will cut the current to the output as soon as an overload condition is
detected. The fuse is a round, yellow-coloured PTC that will change to orange and heat up on an overload
condition. Once power has been removed from the C1000, the fuse will cool down and automatically
reset. Fix the faulty wiring and you will be able to activate the output once again.

Output Specifications

Output
Triac source 24VAC,
1
Max Current: 300 mA
Triac source 24VAC,
2
Max Current: 300 mA
Triac source 24VAC,
3
Max Current: 300 mA
Triac source 24VAC,
4
Max Current: 300 mA
Configurable Analog Output:
- 0 to 10 VDC
5
- 2 to 10 VDC
- 0 to 5 VDC
Max Current: 40 mA
REV. 6.1.6 / PL-HRDW-RTU-C1000-C/F-EN
Type
On-or-Off
On-or-Off
On-or-Off
On-or-Off
Modulating Proportional /
Pulse /
On-or-Off
Action
Application
Fan
Cooling (1st Stage)
Cooling (2nd Stage)
Heating (1st or 2nd
Stage) /
Preheat Permission
Preheating only /
Preheat + Heating /
Heating (1st or 2nd
Stage)
11