Technical Specifications - Prolon C1000 Series Hardware Manual

Rooftop controller
Hide thumbs Also See for C1000 Series:
Table of Contents

Advertisement

Technical Specifications

Supply: 24 VAC ±10%, 50/60 Hz, Class 2
Consumption: 2 VA (Consumption), 32 VA (Input)
Inputs: • Outdoor – thermistor 10K
• Return – thermistor 10K
• Supply – thermistor 10K
• External clock or Proof of fan– dry contact
Digital outputs: 4 triac outputs, 10-30 VAC source or sink, 300 mA max (resettable fuse)
Analog output: 1 output 0-10 VDC / 2-10 VDC / 0-5 VDC, 40 mA max (resettable fuse)
Indication lights (LED): State of each output / Communication / Power / State of microprocessor
Microprocessor: PIC18F6722, 8 bits, 40 MHz, 128KB FLASH memory
Casing: Molded ABS, UL94-HB
Communication: Modbus RTU (RS485), up to 127 nodes
Baud rate: 9600, 19200, 38400, 57600, 76800, 115200
Connection: Removable screw-type terminal blocks (16 AWG max) and RJ45 modular jack
Dimensions: 6.5" x 5.3" (165mm x 135mm)
Environment: 32-122 ºF (0-50 ºC) Non-Condensing
Certification: RoHS, FCC part 15: 2012 class B
The performance specifications are nominal and conform to acceptable industry standards. ProLon Inc. will
not be liable for damages resulting from misapplication or misuse of its products.
REV. 6.1.6 / PL-HRDW-RTU-C1000-C/F-EN