Inputs
Temperature Sensors
The C1000 Rooftop controller has three analog inputs that monitor outside air, return air and supply air
temperatures (see Figure 7) and will integrate these readings into its control sequence. The sensors used
are standard 10k type 3 thermistors that share a single common connection.
Alternatively, the supply air temperature can be retrieved from a zone controller that has its own supply
sensor and belongs to the C1000's network.
The outside air temperature can be also be provided by an alternate source. If a network controller is
present on the network, it can retrieve the outside temperature reading from one controller and
distribute it to any other controllers on the network.
REV. 6.1.6 / PL-HRDW-RTU-C1000-C/F-EN
A
NET
B
OCC
SUPPLY
GND
SETPT
ROOM
Figure 7 - Connecting the Sensors
Supply air sensor
Return air sensor
Outside air sensor