Test operation mode

4.4
Test operation mode
b
CAUTION:
The test operation mode is designed for servo operation confirmation and not for
machine operation confirmation. Do not use this mode with the machine. Always
use the servo motor alone.
If an operation fault occurred, use the forced stop (EM1) to make a stop.
By using a personal computer and the setup-software, you can execute jog operation,
positioning operation, motor-less operation and forced output without connecting the motion
controller.
Use the system setup according to fig. 3-28 and fig. 3-29.
NOTE
For full information of this functions, refer to the setup-software manual.
JOG operation
Jog operation can be performed without using the servo system controller. This operation may
be used independently of whether the servo is on or off and whether the servo system controller
is connected or not.
Exercise control on the jog operation screen of the setup-software.
Speed [r/min]
Acceleration/deceleration time constant [ms]
Tab. 4-5: JOG operation settings
Function
Forward rotation start
Reverse rotation start
Stop
Tab. 4-6: Operation method
MELSERVO J2-Super
Initial value
200
1000
Button
Forward
Reverse
Stop
Operation
Setting range
0 to 5175
0 to 20000
4 - 7