10.17 Example configuration: Indirect activation via the PLC
10.17.1 Task
• Reading of a 10-digit code in 2/5 Interleaved format
• Indirect activation of the BCL
Code sample
Code 2/5 Interleaved 10 digits with check digit
‹z"{,;›
2234234459
10.17.2 Procedure
Hardware, connections
The following connections must have been established:
• Voltage supply (PWR)
• PROFINET-IO (HOST/BUS) In
Required modules
Include the following modules in your project:
• Module 1010 – Activations
• Module 1023 – Decoding result 12 bytes
Parameter settings
No parameters need to be set separately. The standard parameter set provides all required
functions.