Static pressure level (N)
1
2
3
4
5
6
7
8
9
10
For AD105/125/140M1ERG, ADH071M3ERG, ADH105/125/140/160/200/250H1ERG, static pressure level
selection can also /be achieved by Infrared remote controller, method is:
Step a: set the Infrared remote controller at condition:FAN mode, fan speed high.
Step b:then aim the remote controller at the infrared remote receiver RE 02, press HEALTH button 4+N times(1≤N
≤10, integer) within 12 seconds, then the receiver will beep N+1 times, the static pressure level N is been set
successfully.
Note:For Infrared remote controller YR HBS01,need press ON/OFF button make the controller's at OFF status
firstthen open the button cover press FRESH button will enter FAN mode interface.
External static pressure (pa)
ADH105H1ERG ADH125H1ERG
ADH140H1ERG ADH160H1ERG
40
50
60
80
100
120
150
180
200
250
76
Smart Power
ADH200H1ERG ADH250H1ERG
40
72
100
120
150
180
210
230
250
300