Haier Smart Power Series Service Manual page 172

Table of Contents

Advertisement

0151800054H: Dip switch setting Model: 1UH160H1ERG
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
OFF
----
----
ON
----
----
----
OFF
----
----
ON
----
----
----
OFF
----
----
ON
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
SW6 (1-ON, 0-OFF)
SW6-8 SW6-7 SW6-6 SW6-5 SW6-4 SW6-3 SW6-2 SW6-1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
----
----
----
1
1
1
Note:
1. If the outdoor unit connects with centralized controller, the unit no.(displayed on controller) = Unit address+1;
2.The centralized controller includes YCZ-G001,YCZ-A003,YCZ-A004; the max.unit quantity controlled by YCZ-G001 is 32, the
DIP switch setting of SW6-6,SW6-7,SW6-8 must keep all OFF.; for YCZ-A003, it's 128, the DIP switch setting of SW6-8 must
keep OFF; for YCZ-A004, it's 256. no DIP switch setting limitation.
3.The protocal slelection in the centralized controller: for YCZ -G001, no need select protocal; for YCZ-A003, the type select in
"Monitor" must be "Unitary"; for YCZ-A004, the "Type Select" in "System Settings" must be "Single".
SW7 (1-ON, 0-OFF)
SW7-1
SW7-2
0
0
0
1
1
0
1
1
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
OFF
----
----
ON
----
----
----
OFF
----
----
ON
----
----
----
OFF
----
----
ON
----
----
----
OFF
----
----
----
----
----
----
----
----
----
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
0
0
1
0
0
1
----
----
----
1
1
1
Defination
DERD test selection 0
DERD test selection 1
DERD test selection 2
DERD non-test selection
Manually forced operation invalid(default)
----
----
Manually forced operation valid
----
----
Manually forced heating(default)
----
----
Manually forced cooling
----
----
Normal standby cost
----
----
Low stand by power cost(default)
----
----
H.R-R.K module protocol
----
----
H.R-RENE.module protocol (default)
----
----
Central control(default)
----
----
BMS
----
----
Refrigerant R410A(default)
----
----
Refrigerant R32
----
----
Defrost automatic(default)
Defrost by time
ON
Not for base station
----
OFF
Base station application(default)
----
ON
unit No.(display on the controller)
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
----
----
1
1
SW8
7
170
Smart Power
Description
0
1
2
3
4
5
6
7
----
256
Defination
1UH160P1ERK

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents