Vc/s 4.x.1 valve drive controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Dependent parameter
Hysteresis
Options:
This parameter is used to specify the hysteresis that is to apply to the setpoint to prevent continuous
switching of the controller.
Upper switching point = setpoint + hysteresis
Lower switching point = setpoint – hysteresis
Heating controller:
If the actual temperature is below the lower switching point, the controller switches on.
If the actual temperature is above the upper switching point, the controller switches off.
Cooling controller:
If the actual temperature is below the lower switching point, the controller switches off.
If the actual temperature is above the upper switching point, the controller switches on.
Dependent parameter
Activate temperature limitation
Options:
A controller temperature limitation can be activated using this parameter. Using the temperature limitation,
the controller's control value for this stage can be set to 0 on reaching a parameterized temperature.
In this way, exceeding (heating) or dropping below (cooling) this temperature can be prevented.
An example of the usage of the temperature limitation is floor heating, where exceeding a specific
temperature must be prevented to protect the material of the floor.
no: The temperature limitation is deactivated.
yes: The temperature limitation is activated. The following dependent parameters are also displayed.
102 2CDC508220D0211 Rev. A | VC/S 4.x.1
0.3...0.5...25.5 K
No
Yes